ICS Triplex TC-505-02-4M5 4.5-Meter Trusted I/O SmartSlot Cable
Technical Specifications
-
Electrical & Signal Specifications
- Cable Type: 34-core shielded multi-conductor (24 AWG stranded copper)
- Voltage Rating: 300 V AC/DC (continuous operation)
- Current Rating: 2 A per conductor (max load)
- Insulation Resistance: ≥100 MΩ (at 500 V DC)
- Shielding: Foil + braid dual shielding (shielding effectiveness ≥90 dB at 100 kHz–1 GHz)
- Impedance: 120 ohms (signal pairs)
- Capacitance: ≤25 pF per meter (conductor-to-conductor)
- Attenuation: ≤1 dB per meter at 1 MHz
- Signal Isolation: 2500 Vrms (module-to-FTA, 1 minute)
ICS Triplex TC-304-01-5M0 Trusted 5-Meter Maintenance & Diagnostic Cable
Technical Specifications
-
Electrical & Signal Specifications
- Cable Type: 6-core shielded twisted-pair (Belden 9536 equivalent)
- Wire Gauge: 24 AWG (stranded copper conductors for flexibility)
- Impedance: 100 ohms (matched for RS232 signal integrity)
- Voltage Rating: 300 V AC/DC (continuous operation)
- Current Rating: 1 A per conductor (max)
- Insulation Resistance: ≥100 MΩ (at 500 V DC)
- Capacitance: 20 pF per meter (conductor-to-conductor)
- Attenuation: ≤1 dB per meter at 1 MHz
- Shielding Effectiveness: ≥90 dB (at 100 kHz to 1 GHz)
- Communication Protocol: RS232 (asynchronous serial, up to 115.2 kbps).
ICS Triplex TC‑303‑02‑4M0 4‑Meter Trusted Local Expansion Fiber Optic Cable
Technical Specifications
-
Optical Specifications
- Fiber Type: 62.5/125 μm duplex multimode (OM1)
- Core/Cladding Diameter: 62.5 μm core, 125 μm cladding
- Numerical Aperture (NA): 0.275
- Attenuation: ≤3.5 dB/km at 850 nm; ≤1.5 dB/km at 1300 nm
- Insertion Loss: ≤0.3 dB per LC connector (typical: 0.2 dB)
- Return Loss: ≥35 dB (typical: 40 dB)
- Bandwidth: 160 MHz·km at 850 nm; 500 MHz·km at 1300 nm
- Operating Wavelength: 850 nm / 1300 nm (dual‑window compatibility)
-
Electrical & Mechanical Specifications
- Connector Type: LC/LC keyed industrial fiber optic connectors (dust‑cap protected)
- Jacket Material: LSZH (Low Smoke Zero Halogen)
- Strain Relief: Molded black polyurethane strain relief at both ends
- Cable Diameter: 5 mm (0.2 inches)
- Minimum Bend Radius: 25 mm (dynamic); 15 mm (static)
- Tensile Strength: 100 N (22.5 lbf) for short‑term installation; 50 N (11.2 lbf) for long‑term operation
- Length: 4 meters (13.1 feet) ± 0.1 meters (factory‑calibrated)
- Weight: 0.25 kg (0.55 lbs)
ICS Triplex TB8110B Trusted TMR Processor Module
Technical Specifications
-
Processor & Memory
- Processor Clock: 100 MHz RISC (reduced instruction set computing) core
- DRAM: 16 MB EDO with 60 ns access time for real‑time data processing
- EPROM: 512 KB for bootloader and firmware storage
- Flash Memory: 2 MB for application program and OS kernel storage
- NVRAM: 128 KB for maintained variable storage (retained during power loss)
- Variable Storage Allocation: 1 byte per discrete, 4 bytes per analog, 5 bytes per timer
- SOE Buffer: 1000 local events, transfers to CI module buffer (4000 events total)
-
Electrical Specifications
- Power Input: 20–32 VDC (redundant power inputs for fault tolerance)
- Power Consumption: 80 W (heat dissipation: 80 W typical)
- Power Protection: Reverse polarity protection, overvoltage clamping, and current limiting
- I/O Interface: Triple redundant Inter‑Module Bus (IMB) for I/O module communication
- Communication Ports: 2x RS422/485 (2/4‑wire), 1x RS485 (2‑wire), IRIG‑B 002 time sync input
ICS Triplex T9902 10A Fast‑Acting Replacement Output Fuse
Technical Specifications
-
-
Electrical Specifications
- Current Rating: 10A (fast‑acting)
- Voltage Rating: 125 VAC/DC (continuous)
- Breaking Capacity: 100 A at 125 VAC/DC (interrupts fault currents safely)
- Fuse Type: Fast‑acting (class F) for rapid overcurrent response
- Resistance: 0.05 ohms (typical) at 25°C for minimal voltage drop
- Temperature Coefficient: ±0.005 ohms/°C (25°C to 100°C) for stable performance across operating temperatures
- Insulation Material: Ceramic body (high thermal resistance and arc suppression)
- Contact Material: Silver‑plated copper end caps for low‑resistance connections
-
ICS Triplex T9901 50 mA Fast‑Acting Replacement Input Fuse
Technical Specifications
-
Electrical Specifications
- Current Rating: 50 mA (fast‑acting)
- Voltage Rating: 250 VAC/DC (continuous)
- Breaking Capacity: 100 A at 250 VAC/DC (interrupts fault currents safely)
- Fuse Type: Fast‑acting (class F) for rapid overcurrent response
- Resistance: 0.5 ohms (typical) at 25°C for minimal voltage drop
- Temperature Coefficient: ±0.01 ohms/°C (25°C to 100°C) for stable performance across operating temperatures
- Insulation Material: Ceramic body (high thermal resistance and arc suppression)
- Contact Material: Silver‑plated copper end caps for low‑resistance connections
ICS Triplex T9892 8‑Channel Duplex Digital Output Termination Assembly
Technical Specifications
-
Mechanical Specifications
- Form Factor: AADvance standard termination assembly (compatible with T9300 3‑slot backplanes)
- Dimensions: 112 mm (width) × 70 mm (depth) × 123 mm (height) (4.41 in × 2.76 in × 4.84 in)
- Weight: 1.0 kg (2.2 lb)
- Mounting: Plug‑in to T9300 backplanes; tool‑free installation
- Protection Rating: IP20 (dust and finger contact protection)
- Housing Material: Powder‑coated metal alloy with flame‑retardant polymer insulators
- Color: Black (matches AADvance controller chassis)
- Connector Type: Locking screw‑type terminal blocks (2.5 mm² wire capacity)
- Field Power Access: Front‑panel dedicated connectors for dual commoned field power inputs
ICS Triplex T9882 8‑Channel Duplex Isolated Analogue Output Termination Assembly
Technical Specifications
-
Mechanical Specifications
- Form Factor: AADvance standard termination assembly (compatible with T9300 3‑slot backplanes)
- Dimensions: 112 mm (width) × 70 mm (depth) × 123 mm (height) (4.41 in × 2.76 in × 4.84 in)
- Weight: 1.0 kg (2.2 lb)
- Mounting: Plug‑in to T9300 backplanes; tool‑free installation
- Protection Rating: IP20 (dust and finger contact protection)
- Housing Material: Powder‑coated metal alloy with flame‑retardant polymer insulators
- Color: Black (matches AADvance controller chassis)
- Connector Type: Locking screw‑type terminal blocks (2.5 mm² wire capacity)
- Fuse Access: Front‑panel accessible without removing module or termination assembly
ICS Triplex T9881 8‑Channel Simplex Isolated Analogue Output Termination Assembly
Technical Specifications
-
Mechanical Specifications
- Form Factor: AADvance standard termination assembly (compatible with T9300 3‑slot backplanes)
- Dimensions: 112 mm (width) × 70 mm (depth) × 123 mm (height) (4.41 in × 2.76 in × 4.84 in)
- Weight: 1.0 kg (2.2 lb)
- Mounting: Plug‑in to T9300 backplanes; tool‑free installation
- Protection Rating: IP20 (dust and finger contact protection)
- Housing Material: Powder‑coated metal alloy with flame‑retardant polymer insulators
- Color: Black (matches AADvance controller chassis)
- Connector Type: Locking screw‑type terminal blocks (2.5 mm² wire capacity)
- Fuse Access: Front‑panel accessible without removing module or termination assembly
ICS Triplex T9851 8‑Channel Simplex Commoned Digital Output Termination Assembly
Technical Specifications
-
Mechanical Specifications
- Form Factor: AADvance standard termination assembly (compatible with T9300 3‑slot backplanes)
- Dimensions: 112 mm (width) × 70 mm (depth) × 123 mm (height) (4.41 in × 2.76 in × 4.84 in)
- Weight: 1.0 kg (2.2 lb)
- Mounting: Plug‑in to T9300 backplanes; tool‑free installation
- Protection Rating: IP20 (dust and finger contact protection)
- Housing Material: Powder‑coated metal alloy with flame‑retardant polymer insulators
- Color: Black (matches AADvance controller chassis)
- Connector Type: Locking screw‑type terminal blocks (2.5 mm² wire capacity)
- Fuse Access: Front‑panel accessible without removing module or termination assembly
ICS Triplex T9832 16‑Channel Dual Isolated Analogue Input Termination Assembly
Technical Specifications
-
Mechanical Specifications
- Form Factor: AADvance standard termination assembly (compatible with T9300 3‑slot backplanes)
- Dimensions: 112 mm (width) × 70 mm (depth) × 123 mm (height) (4.41 in × 2.76 in × 4.84 in)
- Weight: 1.0 kg (2.2 lb)
- Mounting: Plug‑in to T9300 backplanes; tool‑free installation
- Protection Rating: IP20 (dust and finger contact protection)
- Housing Material: Powder‑coated metal alloy with flame‑retardant polymer insulators
- Color: Black (matches AADvance controller chassis)
- Connector Type: Locking screw‑type terminal blocks (2.5 mm² wire capacity)
- Fuse Access: Front‑panel accessible without removing module or termination assembly
ICS Triplex T9831 16‑Channel Simplex Non‑Isolated Analogue Input Termination Assembly
Technical Specifications
-
Mechanical Specifications
- Form Factor: AADvance standard termination assembly (compatible with T9300 3‑slot backplanes)
- Dimensions: 112 mm (width) × 70 mm (depth) × 123 mm (height) (4.41 in × 2.76 in × 4.84 in)
- Weight: 1.0 kg (2.2 lb)
- Mounting: Plug‑in to T9300 backplanes; tool‑free installation
- Protection Rating: IP20 (dust and finger contact protection)
- Housing Material: Powder‑coated metal alloy with flame‑retardant polymer insulators
- Color: Black (matches AADvance controller chassis)
- Connector Type: Locking screw‑type terminal blocks (2.5 mm² wire capacity)
- Fuse Access: Front‑panel accessible without removing module or termination assembly