FOXBORO FBM237 Channel Isolated Output Interface Module
Technical Specifications
- Output Channels: 8 isolated analog output channels (0–20 mA DC, configurable to 4–20 mA).
- Isolation: Each channel is electrically isolated to prevent cross-talk and ground loop interference.
- Output Range: 0–20.4 mA DC (resolution: 13-bit).
- Load Capacity: Maximum 750 Ω per channel.
- Power Supply: 24 V DC ±5%, -10% (redundant power input supported).
- Power Consption: ≤7 W (maximum).
- Environmental Tolerance:
- Operating Temperature: -20°C to +70°C (-4°F to +158°F).
- Storage Temperature: -40°C to +85°C (-40°F to +185°F).
- Humidity: 5%–95% RH (non-condensing).
- Altitude: -300 to +3,000 m (-1,000 to +10,000 ft).
- Pollution Level: G3 (harsh industrial environments per ISA S71.04).
FOXBORO FBM219 Digital Input/Output Module
Technical Specifications
- Input/Output Channels:
- Typically configured with multiple digital input channels (e.g., 8 or 16 channels) for discrete signal monitoring (e.g., switch status, alarm triggers).
- Some variants support digital output channels for controlling actuators or indicators.
- Signal Types:
- Accepts dry contact signals (e.g., relay outputs) or voltage signals (e.g., 24 V DC).
- Communication Protocols:
- Integrates with the I/A Series system via redundant 2 Mbps fieldbus networks.
- Supports standard industrial protocols like Modbus TCP/RTU for compatibility with third-party devices.
- Power Requirements:
- Operates on 24 V DC ±5% (some variants support 26–42 V DC).
- Power consumption: ≤14 W under normal operating conditions.
FOXBORO FBM217 P0914TR Discrete Input Interface Module
Technical Specifications
- Input Channels: 32 isolated channels, each accepting 2-wire DC voltage inputs.
- Input Voltage Range: Supports signals below 60 V AC, 120 V AC/125 V DC, or 240 V AC via associated terminal assemblies (TA).
- Current Consumption: 2.2 mA (typical) at 30 V DC input.
- Communication Protocol: Connects to redundant 2 Mbps module fieldbuses, enabling communication with associated Field Control Modules (FCM) or Field Control Processors (FCP).
- Power Requirements: 24 V DC ±5%, -10%; consumes 3 W at 24 V DC.
- Physical Dimensions: Approximately 10.2 cm (height) × 11.4 cm (width, including mounting ears) × 4.5 cm (depth) × 10.4 cm.
- Environmental Tolerance: Operates reliably in industrial settings with standard temperature and humidity ranges.
- Certifications: Complies with industrial safety and reliability standards.
FOXBORO FBM216 Industrial Control Module
Technical Specifications
- Input/Output Channels:
- Supports up to 8 isolated channels (configurable for analog or digital signals).
- Signal types: 4–20 mA, 0–10 V, thermocouple inputs (e.g., K, J, T types), and HART digital signals.
- Communication Protocols:
- Ethernet/IP for high-speed data transfer (10/100 Mbps).
- HART protocol for bidirectional communication with smart field devices.
- Modbus RTU/TCP for compatibility with legacy systems.
- Accuracy:
- Analog signal accuracy: ±0.075% full-scale.
- Resolution: 15-bit for precise signal detection.
FOXBORO FBM215 HART® Communication Output Interface Module
Technical Specifications
- Output Channels:
- 8 isolated channels, each configurable for:
- Standard 4–20 mA analog output
- Digital HART FSK signal (superimposed on 4–20 mA)
- 8 isolated channels, each configurable for:
- HART Communication:
- Built-in FSK modem for each channel for HART protocol compliance.
- Supports HART universal commands, common-practice commands, and device-specific commands (excluding burst mode).
- Isolation:
- Channel-to-channel and channel-to-ground isolation (up to 250 V AC).
- Response Time:
- ≤10 ms for analog signals; ≤5 ms for discrete signals.
FOXBORO FBM214B Industrial Control Module
Technical Specifications
- Input/Output Channels:
- Supports up to 8 isolated input channels (configurable based on model variants).
- Signal types: 0–20 mA, 4–20 mA, 0–10 V, and thermocouple inputs (e.g., K, J, T types).
- Accuracy: High-precision analog conversion with ±0.1% full-scale accuracy.
- Isolation: Channel-to-channel and channel-to-ground isolation (up to 250 V AC).
- Response Time: ≤10 ms for analog signals; ≤5 ms for discrete signals.
- Environmental Tolerance:
- Operating temperature: -40°C to +85°C.
- Storage temperature: -40°C to +85°C.
- Humidity: 5%–95% non-condensing.
FOXBORO FBM214 Industrial Control Module
Technical Specifications
- Input/Output Channels:
- Supports up to 8 isolated input channels (specific configurations may vary by model variant).
- Signal types: 0–20 mA, 4–20 mA, 0–10 V, and thermocouple inputs (e.g., K, J, T types).
- Accuracy: High-precision analog conversion with ±0.1% full-scale accuracy.
- Isolation: Channel-to-channel and channel-to-ground isolation (up to 250 V AC).
- Response Time: ≤10 ms for analog signals; ≤5 ms for discrete signals.
- Environmental Tolerance:
- Operating temperature: -40°C to +85°C.
- Storage temperature: -40°C to +85°C.
- Humidity: 5%–95% non-condensing.
- Power Requirements:
- Voltage range: 10 V–30 V DC (FBM214B variant supports 26–42 V DC).
- Power consumption: 14 W (typical).
FOXBORO FBM211 P0916JT I/O Module
Technical Specifications
- Input/Output Channels:
- Supports 16 isolated independent channels (specific configurations may vary by model variant).
- Signal types: 0–20 mA DC (current-limited to 33 mA per channel).
- Accuracy: High-precision analog conversion with ±0.1% full-scale accuracy.
- Isolation: Channel-to-channel and channel-to-ground isolation (up to 250 V AC).
- Response Time: ≤10 ms for analog signals; ≤5 ms for discrete signals.
- Environmental Tolerance:
- Operating temperature: -40°C to +70°C.
- Storage temperature: -40°C to +85°C.
- Humidity: 5%–95% non-condensing.
FOXBORO FBM207C High-Performance Analog Input/Output Module
Technical Specifications
- Input/Output Channels:
- Supports 8 analog input/output channels (configurable based on model variants).
- Signal types: 0–20 mA, 4–20 mA, 0–10 V, thermocouples (e.g., K, J, T types).
- Accuracy: High-precision analog conversion with ±0.1% full-scale accuracy.
- Isolation: Channel-to-channel and channel-to-ground isolation (up to 250 V AC).
- Response Time: ≤10 ms for analog signals; ≤5 ms for discrete signals.
- Environmental Tolerance:
- Operating temperature: -40°C to +70°C.
- Storage temperature: -40°C to +85°C.
- Humidity: 5%–95% non-condensing.
- Power Requirements: 24 V DC ±10%.
- Physical Dimensions: Compact DIN rail-mountable design (approx. 110 mm × 45 mm × 16.8 mm).
- Weight: 0.26–0.5 kg (depending on configuration).
- Certifications: CE, CSA, UL, and GOST for safety and industrial compliance.
FOXBORO FBM207B P0916JS I/O Module
Technical Specifications
- Input/Output Channels:
- Supports a mix of analog and discrete signals (specific configurations vary by model variant).
- Analog inputs: 0–20 mA, 4–20 mA, 0–10 V, or thermocouple signals (e.g., K, J, T types).
- Discrete inputs/outputs: 24 V DC for binary control signals.
- Accuracy: ±0.1% of full scale for analog signals.
- Isolation: Channel-to-channel and channel-to-ground isolation (up to 250 V AC).
- Response Time: ≤10 ms for analog signals; ≤5 ms for discrete signals.
- Environmental Tolerance:
- Operating temperature: -40°C to +70°C.
- Storage temperature: -40°C to +85°C.
- Humidity: 5%–95% non-condensing.
FOXBORO FBM201 Analog Input Module
Technical Specifications
- Input Channels: 8 independent analog input channels.
- Input Types:
- 0–20 mA DC (two-wire transmitters).
- 0–100 mV DC.
- 0–5 V DC.
- 0–10 V DC.
- Accuracy: ±0.03% of full scale (including linearity).
- Temperature Coefficient: ±50 ppm/°C.
- Isolation: Each channel is electrically isolated from others and ground, withstanding 600 V AC for 1 minute.
- A/D Conversion: Sigma-delta conversion per channel, sampling rate of 25 ms per channel.
- Integral Time: Software-configurable to filter process noise and power line frequency interference.
FOXBORO FBM02 I/O Module
Technical Specifications
- Input/Output Types:
- Thermocouple/mV input (e.g., P0400YC model for temperature measurement).
- Analog input channels (e.g., 8 channels with configurable ranges like 4-20 mA, 0-10V).
- Voltage Range:
- Operating voltage: 26-42 VDC (typical for P0400YC).
- Power consumption: 14W (typical).
- Environmental Conditions:
- Operating temperature: -40°C to 85°C (storage: -40°C to 90°C).
- Humidity tolerance: 0.65%-0.7% non-condensing.