Technical Specifications
- Core Processor: PowerPC 604e, 1 GHz main frequency
- System Memory: 512 MB ECC SDRAM
- Local Storage: 4 GB Industrial CompactFlash Card
- Power Supply: 24 VDC ±10%, Max input current 2 A
- Power Consumption: ≤18 W under full load
- Control Capacity: Max 256 PID control loops, 4096 I/O signal points
- Control Cycle Options: 100 ms / 200 ms / 500 ms / 1 s configurable
- Communication Interfaces: 2 × 10/100 Mbps Ethernet (Vnet/IP), 1 × RS-232C maintenance port
- Isolation Grade: 1 kVrms channel-to-power isolation
- Physical Dimension: 100 mm (W) × 240 mm (H) × 125 mm (D)
- Net Weight: 0.5 kg
- Protection Class: IP20 (when installed in standard DCS rack cabinet)
- Operating Temperature: 0 ℃ ~ +55 ℃, non-condensing
- Storage Temperature: -20 ℃ ~ +70 ℃
- Humidity Range: 10% ~ 90% RH, no dew formation
- Vibration Resistance: 10–150 Hz, 0.5 g acceleration compliant with IEC 60068-2-6
Function Features
- Supports full set of industrial PID algorithms including self-tuning, cascade control, feedforward compensation, anti-windup limit
- Built-in real-time operating system with deterministic millisecond-level response for safety interlock logic
- Complete hardware self-diagnosis: power supply detection, memory error check, communication link fault alarm, I/O channel abnormality report
- Native 1:1 hot redundant CPU backup, seamless switch without process interruption
- Vnet/IP high-speed control bus, station internal data refresh cycle ≤50 ms
- Offline program download, online parameter modification without station shutdown
- Historical trend data cache, event log storage for process traceability
- Multi-protocol compatibility: Modbus TCP, Modbus RTU for third-party device interconnection
Performance Parameters
- Arithmetic computing capacity: 1200 MIPS floating-point operation
- Redundant switch time: ≤100 ms without signal loss
- Max expandable I/O unit quantity: 16 pieces per CPU station
- Single I/O unit maximum channel count: 32 points
- Data retention period: 10 years for CF card stored configuration data
- Mean Time Between Failures (MTBF): 120,000 hours under rated operating environment
Material Composition
- Outer housing: Flame-retardant ABS engineering plastic, UL94 V-0 fire rating
- Internal circuit substrate: FR-4 high-temperature resistant PCB with gold-plated contact pins
- Cooling structure: Passive convection heat sink made of aluminum alloy
- Connector terminals: Copper alloy with nickel plating, anti-oxidation coating
Structural Characteristics
- Standard 8-slot DCS rack slide-in modular structure, front-side pluggable without dismounting wiring terminals
- Front panel equipped with LED status indicator array: RUN, ERROR, COM, REDUNDANT status lights
- Rear-side dedicated high-speed backplane bus connector for I/O unit data transmission
- External CF card slot accessible from module front for program backup and restore
- Dual Ethernet RJ45 ports located on front panel for network wiring convenience
Working Principle
The module receives analog/digital field signals from I/O units via backplane bus, converts raw sensor data into standardized engineering values, executes pre-programmed control logic and PID calculation cycles, outputs control commands to corresponding execution I/O channels. It synchronizes real-time process data to operation stations and engineering stations over Vnet/IP industrial Ethernet. Redundant CPU pairs maintain real-time data synchronization through dedicated inter-board bus; upon main CPU failure, standby unit takes over all control tasks instantly without process halt.
Advantage Highlights
- Industrial-grade ECC memory eliminates data corruption caused by electromagnetic interference
- Passive heat dissipation design without fan, zero mechanical wear, low maintenance cost
- Ultra-long MTBF adapts to 24/7 continuous production operation
- Fully isolated signal circuit avoids cross-channel interference in high-EMI industrial sites
- Unified CENTUM VP system compatibility, seamless matching with all Yokogawa I/O modules
- Compact rack layout saves cabinet installation space
- Complete global technical support and spare parts supply network
Applicable Industries
Petroleum refining, natural gas processing, chemical manufacturing, thermal power generation, pharmaceutical fine chemical, water treatment, pulp & paper, food & beverage continuous production, metal smelting
Installation Requirements
- Install inside standard Yokogawa CENTUM VP rack cabinet, DIN rail fixed with locking buckle
- Maintain ≥20 mm vertical clearance above and below module for convection heat dissipation
- Cabinet internal air circulation required, ambient temperature strictly controlled within 0–55 ℃
- Separate power cable and signal wiring to reduce electromagnetic crosstalk
- Earth cabinet grounding terminal with resistance ≤4 Ω
- Do not install adjacent to high-power frequency converter or high-voltage contactor
Usage Precautions
- Power off rack before plugging/unplugging module to prevent backplane bus short circuit
- Only use official Yokogawa CF storage cards; third-party flash media causes data loss risk
- Avoid mechanical impact on module front panel during maintenance
- Do not expose module to corrosive gas, oil mist or conductive dust environment
- Calibrate redundant synchronization bus every 12 months for long-term stable backup
- Do not modify internal circuit components; disassembly voids factory warranty