Technical & Performance Parameters
- Input Channel Quantity: 8 independent galvanic isolation channels
- A/D Conversion Resolution: 16-bit high precision
- Basic Measurement Accuracy: ±0.1% FS @ 25°C ambient temperature
- Full Temperature Zone Accuracy Deviation: ±0.2% FS (-20°C ~ +70°C)
- Supported Input Signal Types: 4–20 mA DC, 0–10 V DC, K/E/J/T thermocouple, Pt100 RTD
- Channel Isolation Withstand Voltage: 500 V AC between channel and system bus, 1 minute withstand test
- Built-in CJC Cold Junction Compensation Accuracy: ±1°C
- Signal Sampling Period: 125 ms–1 s software configurable
- Common Mode Rejection Ratio: ≥120 dB @ 50/60 Hz industrial frequency interference
- Module Power Consumption: 540 mA @ 24 V DC backplane power supply
- Operating Temperature Range: -20 °C ~ +70 °C
- Humidity Working Range: 5%–95% RH non-condensing
- Physical Dimensions: 30 mm (W) × 180 mm (H) × 140 mm (D)
- Net Weight: 0.3 kg
- Certifications: CE, UL safety certification
Material Composition
- Module outer frame: Black flame retardant engineering plastic injection molding shell
- Main PCB substrate: Low-temperature drift FR4 multi-layer circuit board
- Isolation components: Channel independent miniature signal isolation transformer
- Terminal connector: Phosphor bronze gold-plated spring terminal clamp
- Cold junction compensation component: High-precision platinum temperature sensing chip
- Internal passive components: Low-temperature drift metal film precision resistors, polyester filtering capacitors
Structural Characteristics
- Standard Yokogawa CENTUM system backplane pluggable card structure, hot-swap maintenance supported
- Front panel independent channel signal LED indicator light, single channel fault red light alarm
- Separate terminal wiring base TB37G/TB38G matched installation, wiring space reserved for each channel
- Internal independent signal conditioning circuit for each channel, no shared analog processing components
- Vertical heat dissipation channel reserved between front panel and circuit board, avoid heat accumulation
- Anti-slip locking buckle on both sides of module, fixed after inserting backplane to prevent vibration loosening
Working Principle
- Field temperature, pressure, flow analog signals enter each independent isolation channel through matched TB37G terminal base
- Isolation transformer cut off ground loop interference between field equipment and DCS control system
- Thermocouple signal input channel activates built-in CJC cold junction compensation chip to eliminate cold end temperature measurement error
- Precision signal conditioning circuit filter industrial frequency interference and amplify weak sensor signals
- 16-bit A/D converter converts analog measurement signals into digital data
- On-board communication chip transmits digital measurement data to CENTUM main controller via ESB internal system bus
- Real-time self-diagnosis circuit detect channel open circuit, short circuit and over-range signal faults, trigger front panel channel alarm indicator
Core Function Features
- Universal multi-signal compatible input, single module support current, voltage, thermocouple and RTD temperature sensors
- Independent galvanic isolation for every channel, eliminate cross-channel signal crosstalk
- Built-in high-precision cold junction compensation circuit for thermocouple measurement
- High common mode rejection ratio ≥120 dB, strong suppression of on-site industrial frequency electromagnetic interference
- Software configurable sampling period, adapt to fast response pressure signal and slow response temperature signal measurement
- ESB dedicated DCS bus communication, high-speed stable data transmission with Yokogawa CENTUM control system
- Support dual redundant backup configuration for high-reliability safety instrument systems
Advantage Highlights
- Universal multi-signal compatibility, reduce DCS cabinet different module types and save cabinet space
- Full-channel independent isolation, zero interference between different types of field sensor signals
- Ultra-low full-temperature measurement deviation, stable precision under factory seasonal temperature change
- Compact thin thickness design, high cabinet module installation density
- Standard matched TB37G/TB38G terminal base with lightning protection optional configuration
- CE and UL international safety certification, meet petrochemical explosion hazardous area control cabinet standard
Applicable Industries
Petrochemical refining, chemical process production, thermal power plant DCS control, pharmaceutical fine chemical, water supply & wastewater treatment, natural gas pipeline monitoring
Installation Requirements
- Insert into dedicated analog input slot of Yokogawa CENTUM CS3000 / VP backplane, lock side buckle tightly
- Matched TB37G or TB38G terminal base must be installed below module for field signal wiring
- Field sensor wiring uses shielded twisted pair cable, shielding layer single-point grounding inside DCS cabinet
- Reserve ≥10 mm heat dissipation gap between adjacent modules to ensure air circulation
- For intrinsically safe explosion-proof area application, matched isolation safety barrier must be installed on front end of signal wiring
- Ambient cabinet temperature must be controlled within -20°C ~ +70°C operating range, install cooling fan for high-temperature workshop
Usage Precautions
- Do not input over-range voltage/current signal into channel, will damage internal signal conditioning circuit
- Thermocouple wiring must use dedicated temperature compensation cable, ordinary copper wire causes large measurement error
- Strictly prohibit reverse connection of 24 V DC backplane power supply terminal, permanent damage to module power circuit
- Do not disassemble plastic shell without authorization, internal isolation circuit structure will be destroyed
- Regularly clean terminal base dust every 6 months to prevent poor wiring contact
- When single channel alarm occurs, first check field sensor wiring continuity before replacing module