Foxboro SAC-RL100-M11 Relay Output Module

Product Name: Foxboro SAC-RL100-M11 Relay Output Module

Product Series: Foxboro I/A Series — SAC (Series Analog Control) Relay Output Module Family

Product Introduction:
The SAC-RL100-M11 is a 16-channel relay output module for the Foxboro I/A Distributed Control System (DCS). It provides 16 independent SPDT (Single Pole Double Throw) dry contact relay outputs for controlling external devices such as solenoid valves, motor starters, indicator lamps, and alarm annunciators. The module is installed in the I/A Series I/O cabinet and communicates with the controller via the I/A Series backplane bus.

Category:
Description

Technical Specifications:

  • Number of Channels16 SPDT dry contact relay outputs
  • Contact Rating5 A at 250 V AC (resistive load); 5 A at 30 V DC (resistive load)
  • Contact Type: SPDT (Form C) — Common, Normally Open (NO), Normally Closed (NC)
  • Coil Voltage: 24 V DC (nominal), range 18–30 V DC
  • Isolation Voltage: 1500 V DC between channels and backplane
  • Response Time: < 10 ms (typical)
  • Operating Temperature: 0°C to +60°C (+32°F to +140°F)
  • Storage Temperature: -40°C to +85°C (-40°F to +185°F)
  • Humidity: 5% to 95% RH (non-condensing)
  • Power Consumption< 8 W (typical, all relays energized)
  • Dimensions (W x H x D): 25 mm x 220 mm x 160 mm (approximate, DIN rail module)
  • Weight: Approximately 350 grams
  • Backplane ConnectionI/A Series standard backplane connector

Functional Features:

  • 16 Independent Relays: Each relay is individually addressable and controllable by the I/A Series controller
  • Dry Contact Outputs: No voltage supplied by the module — field wiring provides the switched voltage
  • LED IndicatorsPer-channel LED indicates relay state (ON = green, OFF = dark)
  • Backplane Powered: Draws all operating power from the I/A Series backplane — no external power required
  • Hot-Swappable: Module can be replaced without shutting down the I/A Series controller (with proper procedure)

Material Composition:

  • Housing: Flame-retardant ABS plastic (UL 94 V-0)
  • Relay ContactsSilver-cadmium oxide (AgCdO) for high reliability and low contact resistance
  • PCBFR-4 epoxy glass with conformal coating
  • Connectors: Gold-plated edge connector for backplane; screw terminals for field wiring
  • Terminal BlocksPhosphor bronze, tin-plated

Structural Characteristics:

  • Form Factor: DIN rail mountable module for I/A Series I/O cabinet
  • Mounting: Standard 35 mm DIN rail inside I/O cabinet
  • Terminal Layout: 16 groups of 3 terminals per channel (COM, NO, NC)
  • Status LEDs: 16 individual LEDs on front face, one per channel

Working Principle:
The I/A Series controller sends a digital command via the backplane bus to the SAC-RL100-M11 module. The module’s internal decoder activates the corresponding relay driver circuit, which energizes the 24 V DC relay coil. The relay contacts switch from NC to NO (or vice versa). The per-channel LED illuminates when the relay is energized. The dry contact outputs are completely isolated from the module’s internal circuitry — the field device provides its own voltage/current through the relay contacts.

Advantages / Highlights:

  • 16 relay outputs in a single module — reduces cabinet space and wiring complexity
  • 5 A contact rating handles solenoid valves, small motors, and indicator lamps directly
  • Dry contact design provides maximum flexibility — any voltage/current within rating can be switched
  • 1500 V DC isolation ensures noise immunity and ground loop elimination
  • Backplane-powered — no external power supply needed
  • Hot-swappable with I/A Series system

Applicable Industries:

  • Oil and Gas (valve control, pump interlocks)
  • Chemical Processing (solenoid valve sequencing, alarm annunciation)
  • Power Generation (breaker control, pump sequencing)
  • Water Treatment (valve and pump control)
  • Manufacturing (conveyor control, machine interlocks)

Installation Requirements:

  • Install on 35 mm DIN rail inside the I/A Series I/O cabinet
  • Ensure backplane connector is fully seated — improper seating causes communication failure
  • Connect field device wiring to COM, NO, and NC terminals for each channel
  • Do not exceed 5 A per contact — use external contactor for higher loads
  • Do not apply backplane power to field wiring — relays are dry contact only
  • Maintain minimum 10 mm clearance above and below module for ventilation

Usage Precautions:

  • Verify relay contact rating (5 A / 250 V AC) before connecting inductive loads — use snubber circuits for inductive loads
  • Do not exceed 30 V DC coil voltage — will damage relay driver circuitry
  • For inductive loads (solenoids, relays), install a flyback diode across the load to suppress voltage spikes
  • Do not mix AC and DC loads on the same relay contact without verifying rating
  • Replace module immediately if any LED fails to illuminate when commanded
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “Foxboro SAC-RL100-M11 Relay Output Module”

Your email address will not be published. Required fields are marked *

Shipping and Delivery

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.