Foxboro P0917MF Smart Pressure Transmitter

Product Name: Foxboro P0917MF Smart Pressure Transmitter

Product Series: P0917 Series — Gauge Pressure Transmitter

Product Introduction:
The Foxboro P0917MF is a smart gauge pressure transmitter from the P0917 series, configured for very low-pressure range applications. It is ideal for measuring low pressures such as draft, fan pressure, filter differential monitoring, and HVAC system pressures. It features HART 5/7 communication and silicon resonant sensing.

Category:
Description

Model Designation Breakdown:

  • P0917 = Pressure Transmitter Series (Low Range Variant)
  • MF = Range Code: 0–30 psi (0–207 mbar)
  • Process Connection: 1/2 NPT Male (Bottom Mount)

Technical Specifications:

Parameter Value
Measurement Type Gauge Pressure
Range 0 – 30 psi (0 – 207 mbar / 0 – 207 kPa)
Output Signal 4 – 20 mA DC + HART 5/7 Protocol
Accuracy ±0.04% of URL
Long-Term Stability ±0.1% of URL per 5 Years
Process Connection 1/2 NPT Male (Bottom Mount)
Electrical Connection 1/2 NPT Conduit Entry
Wetted Materials Hastelloy C-276
Housing Material 316L Stainless Steel
Process Temperature -40°C to +120°C (-40°F to +248°F)
Ambient Temperature -40°C to +85°C (-40°F to +185°F)
Supply Voltage 12 – 42 V DC
Load Resistance (HART) 230 – 600 Ω
Protection Rating IP67 (NEMA 4X)
Intrinsic Safety IS (Ex ia IIC T4/T5/T6)
Flameproof Ex d IIC T6 (Option Available)
SIL Rating SIL 2 (IEC 61508)
Approvals ATEX, IECEx, FM, CSA, CCC

Working Principle:
Silicon resonant sensor (SenSys) — low-pressure deflection of the silicon diaphragm produces a measurable frequency shift. The onboard microprocessor converts this into a 4–20 mA output with HART 5/7 protocol for remote configuration.

Key Features:

  • Ultra-low range: 0–30 psi (207 mbar) — Optimized for low-pressure applications
  • ±0.04% URL accuracy — Even at low ranges
  • HART 5/7 communication — Full diagnostics and configuration
  • Fast response: < 100 ms — Captures rapid pressure fluctuations
  • Overpressure rating: 45 psi (310 kPa)

Applicable Industries:
HVAC, Building Management Systems, Cleanrooms, Filter Monitoring, Draft Pressure, Fan/Blower Systems, Laboratory Equipment

Installation Requirements:

  • Bottom-mount with 1/2 NPT process connection
  • For gas/air service — ensure no liquid accumulation in impulse lines
  • Use short, straight impulse tubing to minimize lag
  • Install away from vibration sources

Usage Notes:

  • Do not exceed 45 psi (310 kPa) overpressure
  • Zero calibration must be performed at installation conditions
  • HART communication: Use 250 Ω resistor minimum in loop
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “Foxboro P0917MF Smart Pressure Transmitter”

Your email address will not be published. Required fields are marked *

Shipping and Delivery

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.