Technical Specifications:
- Input Channels: 2 universal inputs (independent)
- Input Types: Type J, K, T, E, S, R, B TC; Pt100, Pt1000 RTD; 4–20 mA; 0–10 V; 1–5 V
- Display: Dual-line 6-digit red LED, 14 mm digits, 100,000 count
- Alarm Outputs: 4 SPDT relays (2 Hi + 2 Lo per channel), 250 V AC / 30 V DC, 3 A each
- Communication: RS-485 Modbus RTU, 9600–38400 baud
- Retransmission: Isolated 4–20 mA per channel
- Power Supply: 85–265 V AC / 90–300 V DC / 24 V DC
- Operating Temperature: -10°C to +55°C (+14°F to +131°F)
- Protection Rating: IP65 front panel
- Dimensions: 96 mm x 96 mm x 90 mm (W x H x D)
- Cutout Size: 92 mm x 92 mm
- Weight: Approximately 430 grams
Functional Features:
- 4 Programmable Alarms: 2 High and 2 Low setpoints per channel — supports pre-alarm, alarm, and shutdown hierarchy
- Independent Hysteresis: Each alarm has independently adjustable hysteresis (0.1% to 20% of span)
- Alarm Latching: Relays latch in alarm state until manually reset via keypad or remote command
- Dual Display: Simultaneous real-time display of both process variables
- Peak/Valley Hold: Per-channel peak and valley capture
Material Composition:
- Front Bezel: Flame-retardant ABS, matte black
- Housing: Polycarbonate (Lexan), IP65 gasket seal
- Display: High-brightness red LED, optical-grade polycarbonate
- Terminals: Phosphor bronze, nickel-plated
Structural Characteristics:
- Form Factor: 96 x 96 mm panel-mount (1/4 DIN)
- Keypad: 8-button membrane with dedicated alarm configuration menu
- Communication Port: RJ-11 jack (rear panel)
- Alarm Terminals: 8 screw terminals (AL1-H, AL1-L, AL2-H, AL2-L, AL3-H, AL3-L, AL4-H, AL4-L)
Working Principle:
Each of the two input channels is processed by an independent 24-bit ADC. The microcontroller continuously compares each process value against 4 user-programmable setpoints (2 Hi, 2 Lo) with independent hysteresis. When a setpoint is crossed, the corresponding SPDT relay changes state and latches. The RS-485 Modbus interface allows remote reading of all process values and alarm statuses. The dual LED displays show real-time values for both channels simultaneously.
Advantages / Highlights:
- 4 alarm relays per unit eliminate need for external alarm annunciator modules
- Independent hysteresis per alarm prevents relay chatter on boundary conditions
- Latching relays ensure alarm conditions are not missed during brief excursions
- Dual-channel monitoring with full alarm coverage on both channels
- IP65 rating for harsh industrial environments
Applicable Industries:
- Oil and Gas (safety-critical monitoring)
- Chemical Processing (hazardous area monitoring)
- Power Generation (turbine/boiler protection)
- Mining (safety interlocks)
- Water Treatment (pump protection)
Installation Requirements:
- Cut 92 mm x 92 mm panel opening
- Mount with IP65 gasket and snap-in clips
- Wire field inputs to Ch1 and Ch2 terminal blocks
- Connect alarm relay outputs to AL1 through AL4 terminals
- RS-485: A, B, GND with 120 Ω termination at bus ends
- Power: 85–265 V AC or 24 V DC to L/N or +/- terminals
Usage Precautions:
- Do not exceed 3 A per relay contact — use external contactor for motor-driven loads
- Set hysteresis appropriately — too low causes relay chatter; too high reduces alarm sensitivity
- Verify all 4 alarm setpoints before placing in service
- Test all relays using the keypad test function during commissioning
- Do not apply voltage signals to mA input terminals
Reviews