Technical Specifications
- Form Factor Length: 6-inch non-redundant IOTA chassis
- Supported IOM Quantity: Single analog input IOM per CC-TAIX01
- Field Terminal Count: 16 channel screw terminal pairs
- Signal Compatibility: 4–20 mA HART / non-HART analog input signals, RTD, thermocouple
- Overvoltage Protection Rating: 30 VDC transient surge withstand
- Isolation Barrier Voltage: 2500 VAC channel-to-backplane isolation
- Wiring Terminal Torque Specification: 0.8 N·m recommended tightening torque
- Supported Wire Gauge: 24 AWG to 14 AWG solid/stranded copper
- Operating Temperature Range: -40 °C to +70 °C
- Physical Dimensions: 152 mm × 105 mm × 28 mm
- Net Weight: 0.22 kg
Functional Features
- Integrated transient voltage suppression (TVS) diodes for field surge protection
- Built-in HART signal coupling circuit for bidirectional HART instrument communication
- Independent channel galvanic isolation to eliminate ground loop interference
- Labeled terminal block mapping aligned with Experion PKS channel numbering
- Rear edge connector direct mechanical and electrical mating with analog input IOM
- DIN rail mounting bracket pre-installed for cabinet rack fixation
Performance Parameters
- HART signal passband: 1200 Hz standard HART frequency
- Terminal contact resistance: ≤ 10 mΩ per channel pair
- Surge protection response time: <1 ns
Material Composition
- Chassis Housing: UL94 V-0 flame retardant PA66 plastic
- Terminal Screws: Nickel-plated high-strength steel
- Terminal Contact Blocks: Copper alloy with gold plating
- Internal PCB: FR-4 industrial circuit board with conformal anti-corrosion coating
Structural Characteristics
- Compact 6-inch narrow non-redundant IOTA footprint
- Front exposed screw terminal block for field wiring access
- Rear male edge connector locks onto analog input IOM female port
- Integrated DIN rail clip for quick slide-on rack installation
- Segmented internal PCB layout separating high-voltage surge circuits and low-level analog signal paths
Working Principle
Receives raw analog sensor signals from field cables via front screw terminals; internal TVS surge circuits suppress transient electrical spikes; isolated signal conditioning circuits route conditioned analog and superimposed HART digital signals through rear edge connector to paired analog input IOM module. Channel isolation barriers block cross-channel noise and ground potential differences between field instruments and DCS backplane.
Advantage Highlights
- All field wiring terminated on IOTA base, IOM module can be hot-swapped without field cable disconnection
- Native HART signal multiplexing eliminates external HART interface hardware
- Built-in surge protection reduces external signal isolator hardware requirements
- Compact 6-inch design minimizes cabinet space consumption for non-redundant analog input racks
- Standardized terminal labeling reduces field wiring configuration errors
Applicable Industries
All process industries utilizing 4–20 mA HART transmitters: petrochemical, oil & gas, power plant, water treatment, food processing
Installation Requirements
- Must mate exclusively with non-redundant Series-C analog input IOM (CC-PAIX01, CC-PAIH01)
- Mount on standard 35 mm DIN rail inside Class 1 industrial control cabinet
- Field analog wiring must use shielded twisted-pair cable, shield grounded only at IOTA terminal earth lug
- Maintain minimum 10 mm horizontal gap between adjacent IOTA units for heat dissipation
- Earth terminal of CC-TAIX01 must connect to cabinet protective earth bus bar
Usage Precautions
- Do not apply voltage exceeding 30 VDC transient to any field input terminal
- Avoid routing high-current power cables parallel to analog wiring connected to CC-TAIX01 terminals
- Do not over-tighten terminal screws beyond 0.8 N·m torque rating to prevent plastic terminal block cracking
- Confirm HART instrument loop resistance complies with IOM signal detection range before commissioning
- Regular visual inspection of terminal screw tightness during quarterly cabinet maintenance