Technical Specifications
- Form Factor Length: 9-inch non-redundant chassis
- Supported IOM Quantity: Single digital output IOM per CC-TDOB01
- Digital Output Terminal Count: 32 discrete output channel pairs
- Nominal Output Load Voltage: 24 VDC sinking/sourcing transistor drive
- Per-Channel Continuous Current Limit: 0.5 A maximum
- Inductive Load Flyback Suppression Rating: 40 VDC transient absorption
- Channel-to-Bus Galvanic Isolation Voltage: 2500 VAC
- Terminal Screw Torque Requirement: 0.8 N·m tightening torque
- Supported Wire Gauge: 24 AWG to 14 AWG copper solid/stranded wire
- Operating Temperature Range: -40 °C to +70 °C
- Physical Dimensions: 228 mm × 105 mm × 28 mm
- Net Weight: 0.31 kg
Functional Features
- Independent per-channel electronic short-circuit current limiting protection
- Built-in flyback suppression diodes for inductive solenoid and motor coil loads
- Full channel galvanic isolation separating field actuator wiring and DCS backplane circuits
- Front labeled terminal block mapped to Experion PKS discrete output channel addressing
- Rear edge connector mechanical lock mating with CC-PDOB01 digital output IOM module
- Pre-installed DIN rail mounting clip with anti-slip vibration lock
Performance Parameters
- Per-channel maximum continuous load current: 0.5 A
- Total module aggregate maximum output current: 4 A
- Inductive load transient suppression response time: <1 ns
- Terminal contact resistance: ≤ 10 mΩ per output channel pair
Material Composition
- Chassis Housing: UL94 V-0 flame retardant PA66 glass-filled plastic
- Terminal Hardware: Nickel-plated steel fastening screws, gold-plated copper contact blocks
- Internal PCB: FR-4 high-temperature industrial circuit board with conformal moisture-resistant coating
Structural Characteristics
- 9-inch high-density non-redundant IOTA chassis for 32 discrete output channels
- Front full-width screw terminal bank for field actuator wiring termination
- Single rear edge connector locking onto digital output IOM female port
- Full-length DIN rail mounting base for stable rack fixation under industrial vibration
Working Principle
Receives digital control output signals from paired CC-PDOB01 IOM module via rear edge connector; internal drive conditioning circuits generate regulated 24 VDC sinking/sourcing output signals routed to front field actuator terminals. Per-channel current limiting circuits cut off output drive current upon field wiring short circuit to prevent IOM hardware damage. Integrated flyback suppression diodes absorb voltage transients generated by inductive solenoid and motor coil loads during power switching cycles; galvanic isolation barriers eliminate cross-channel noise and ground loop interference between DCS rack and field actuators.
Advantage Highlights
- Built-in inductive load flyback suppression eliminates external freewheeling diode wiring for solenoid valves
- Per-channel independent short-circuit protection prevents single channel fault from disabling entire module
- 32-channel high-density layout minimizes cabinet space for large discrete actuator control systems
- Non-redundant cost-effective design for non-safety critical discrete control loops
- IOM hot-swap capable without field actuator cable disconnection during maintenance
Applicable Industries
General discrete process actuator control: packaging machinery, conveyor valve solenoids, industrial lighting control, water pump starter control, HVAC damper actuators, food manufacturing line automation
Installation Requirements
- Mandatory pairing with CC-PDOB01 non-redundant digital output IOM module
- Mount on standard 35 mm DIN rail inside Class 1 industrial control cabinet
- Discrete actuator wiring uses shielded twisted-pair cable, single-point shield grounding at IOTA earth lug
- Maintain minimum 10 mm vertical clearance above chassis for passive heat dissipation
- Dedicated cabinet protective earth bus hardwired to CC-TDOB01 ground terminal screw
Usage Precautions
- Do not connect field actuator loads drawing more than 0.5 A continuous per single channel
- Aggregate total output load across all 32 channels must not exceed 4 A continuous total module rating
- Separate high-current motor power wiring from discrete output control cables connected to CC-TDOB01
- Do not over-tighten terminal screws beyond specified torque rating to prevent plastic terminal block cracking
- Inductive solenoid loads with high inrush current require inrush current limiting resistors added to field wiring
Reviews