ABB HIEE300936R0001 UFC718AE01 HIEE300885R0001 PPC380AE01
Technical Specifications
- Output Signal Types:
- Current signals: 4-20 mA DC (sinking/sourcing configurable; compatible with 2-wire/4-wire actuators)
- Voltage signals: 0-10 V DC, ±10 V DC (bipolar)
- Number of Output Channels: 8 independent analog output channels (channel-to-channel isolation)
- Output Resolution: 16-bit DAC (Digital-to-Analog Converter)
- Output Accuracy:
- 4-20 mA DC: ±0.1% of full scale (FS) at 25°C
- 0-10 V DC/±10 V DC: ±0.1% of full scale (FS) at 25°C
- Output Load Capacity:
- Current output (4-20 mA): Maximum 600 Ω (supports long cable runs)
- Voltage output (0-10 V/±10 V): Minimum 1 kΩ (ensures stable voltage delivery)
- Output Protection:
- Short-circuit protection: Current limiting (max 30 mA per channel) with auto-recovery
- Reverse polarity protection: Diode-based circuitry
- Overvoltage protection: 36 V DC clamp
ABB HIEE300890R0001
Technical Specifications
- Input Signal Types:
- Current signals: 4-20 mA DC (compatible with 2-wire and 4-wire transmitters)
- Voltage signals: 0-10 V DC, ±10 V DC (bipolar), 0-5 V DC
- Temperature-compatible signals: Supports input from RTDs (Pt100, Pt1000) and thermocouples (Type J, K, T, E) when paired with compatible signal conditioners
- Number of Input Channels: 8 independent analog input channels (channel-to-channel isolation)
- Input Resolution: 16-bit ADC (Analog-to-Digital Converter) for high-fidelity signal conversion
- Measurement Accuracy:
- For 4-20 mA DC: ±0.1% of full scale (FS) at 25°C (ambient temperature)
- For 0-10 V DC/±10 V DC: ±0.1% of full scale (FS) at 25°C
- For 0-5 V DC: ±0.15% of full scale (FS) at 25°C
- Isolation:
- Channel-to-channel isolation: 500 V AC (rms) for 1 minute (prevents cross-channel interference and ground loops)
- Module-to-backplane isolation: 1500 V AC (rms) for 1 minute (protects the control system backplane from field voltage spikes)
ABB GDB021BE01 HIEE300766R0001
Technical Specifications
- Input Signal Type: Discrete digital signals (dry contact or voltage-driven on/off signals)
- Number of Input Channels: 16 independent digital input channels (group-isolated configuration: 4 channels per isolation group)
- Input Voltage Range:
- Nominal voltage: 24 V DC (standard industrial low-voltage supply)
- Operating voltage tolerance: 19.2 V DC to 30 V DC (accommodates field power fluctuations)
- Input Current:
- "On" state (active): Maximum 7 mA per channel (at 24 V DC)
- "Off" state (inactive): Maximum 0.1 mA per channel (minimizes power consumption)
- Input Thresholds:
- "On" threshold (voltage to detect active state): ≥16 V DC
- "Off" threshold (voltage to detect inactive state): ≤5 V DC
ABB FM9925A-E HIEE451116R0001
Technical Specifications
- Signal Input Types:
- Electrical signals: AC voltage (0-1000 V rms), AC current (0-50 A rms, via current transformers/CTs), DC voltage (0-1000 V), DC current (0-10 A)
- Pulse signals: Digital pulse inputs (0-24 V DC, for encoder or counter signals)
- Signal Processing Performance:
- Sampling rate: Up to 1 MHz per input channel (enables capture of high-frequency transients)
- Signal resolution: 24-bit ADC (Analog-to-Digital Converter) for ultra-high precision
- Frequency response: DC to 50 kHz (covers most industrial and power system signal bandwidths)
- Input Channels:
- 8 analog input channels (for voltage/current signals, fully isolated)
- 4 digital pulse input channels (for high-speed counting or event detection)
- Accuracy:
- For AC voltage (50/60 Hz): ±0.05% of full scale (FS) at 25°C
- For AC current (50/60 Hz): ±0.05% of full scale (FS) at 25°C
- For DC voltage/current: ±0.02% of full scale (FS) at 25°C
ABB CSA464AE HIEE400106R0001 Analog/Digital I/O Card
Technical Specifications
- Input and Output Parameters
- Number of I/O Points: 32 digital inputs and 32 digital outputs.
- I/O Signal Type: Both digital input and output signals are DC 24V.
- I/O Current Range: Digital input current ≤ 7mA, digital output current ≤ 500mA.
- I/O Voltage Range: Digital input and output voltage ranges are both DC 0-30V.
- I/O Response Time: Both digital input and output signal response times are ≤ 1ms.
- High-Speed Counter Input: Supports 4 high-speed counter inputs with a maximum input frequency of 100kHz.
- Power Parameters
- Power Supply Voltage: DC 24V.
- Maximum Power Consumption: 6W.
- Physical and Environmental Parameters
- Dimensions: 130mm (height) × 35mm (width) × 130mm (depth).
- Weight: Approximately 0.3kg.
- Operating Temperature Range: -25℃ to +70℃.
- Communication Parameters
- Communication Interface: RS485 serial interface.
- Communication Protocol: Modbus RTU.
ABB UFC718AE01 HIEE300936R0101
Technical Specifications
- Output Signal Types:
- Current signals: 4-20 mA DC (sinking/sourcing configurable, 2-wire/4-wire compatible)
- Voltage signals: 0-10 V DC, ±10 V DC (bipolar)
- Number of Output Channels: 8 independent analog output channels (channel-to-channel isolation)
- Output Resolution: 16-bit DAC (Digital-to-Analog Converter) for high-fidelity signal generation
- Output Accuracy:
- For 4-20 mA DC: ±0.1% of full scale (FS) at 25°C (ambient temperature)
- For 0-10 V DC/±10 V DC: ±0.1% of full scale (FS) at 25°C
- Output Load Capacity:
- Current output (4-20 mA): Maximum 600 Ω (supports long cable runs and multiple series-connected devices)
- Voltage output (0-10 V/±10 V): Minimum 1 kΩ (ensures stable voltage delivery to low-impedance loads)
- Output Protection:
- Short-circuit protection: Current limiting (maximum 30 mA per channel) with auto-recovery after fault clearance
- Reverse polarity protection: Diode-based circuitry (guards against incorrect field wiring)
- Overvoltage protection: 36 V DC clamp (prevents damage from field power surges)
ABB UBC717AE01 HIEE300927R0101
Technical Specifications
- Output Signal Type: Discrete digital outputs (voltage-driven, solid-state switching)
- Number of Output Channels: 16 independent digital output channels (group-isolated configuration)
- Output Voltage Range:
- Nominal voltage: 24 V DC (standard industrial low-voltage supply)
- Operating voltage tolerance: 19.2 V DC to 30 V DC (accommodates field power fluctuations)
- Output Current Capacity:
- Maximum continuous current per channel: 2 A (supports high-load devices like small motors or solenoids)
- Maximum inrush current per channel: 5 A (peak, for 100 ms, to handle startup surges of inductive loads)
- Maximum total current per module: 16 A (sum of all active channels)
ABB UAC389AE02 HIEE300888R0002
Technical Specifications
- Input Signal Types:
- Current signals: 4-20 mA DC (2-wire/4-wire transmitter compatible)
- Voltage signals: 0-10 V DC, ±10 V DC (bipolar), 0-5 V DC
- Temperature signals (via external transmitters): Supports input from RTDs (Pt100, Pt1000) and thermocouples (Type J, K, T, E) when paired with signal conditioners
- Number of Input Channels: 8 independent analog input channels (channel-to-channel isolation)
- Input Resolution: 16-bit ADC (Analog-to-Digital Converter) for high-fidelity signal conversion
- Measurement Accuracy:
- For 4-20 mA DC: ±0.1% of full scale (FS) at 25°C (ambient temperature)
- For 0-10 V DC/±10 V DC: ±0.1% of full scale (FS) at 25°C
- For 0-5 V DC: ±0.15% of full scale (FS) at 25°C
- Isolation:
- Channel-to-channel isolation: 500 V AC (rms) for 1 minute (prevents cross-channel interference)
- Module-to-backplane isolation: 1500 V AC (rms) for 1 minute (protects the control system backplane from field voltage spikes)
ABB KUC321AE HIEE300698R1
Technical Specifications
- Processor & Computing Performance:
- 32-bit RISC processor (optimized for industrial control tasks)
- Instruction execution speed: Up to 100 MIPS (millions of instructions per second)
- Control task cycle time: Minimum 1 ms (for high-priority real-time control loops)
- Memory Capacity:
- Program memory: 16 MB (non-volatile flash memory, for storing control programs and configuration data)
- Data memory: 32 MB (volatile SRAM, for real-time data processing and temporary variable storage)
- Expandable via external memory cards (support for SD cards up to 32 GB, for data logging or program backup)
- Communication Interfaces:
- Internal: ABB proprietary backplane bus (for communication with I/O modules, maximum 100 Mbps data rate)
- External: 2 x Ethernet ports (RJ45 connectors, 10/100/1000 Mbps Gigabit Ethernet, supporting TCP/IP, UDP, and ABB’s AC 800M system protocols)
- Optional: 1 x RS-232 serial port (for local configuration or maintenance via a laptop)
ABB AFC094AE02 HIEE200130R0002
Technical Specifications
- Supported Communication Protocols:
- Primary protocols: Profibus-DP (slave mode), Modbus RTU (master/slave modes), and Ethernet/IP (adapter mode)
- Supplementary protocol: ABB proprietary SPA (Serial Peripheral Access) bus for internal system communication
- Communication Ports:
- 1 x Profibus-DP port (RS-485 physical layer, baud rate up to 12 Mbps)
- 1 x Modbus RTU port (RS-485 physical layer, baud rate range: 9600 bps to 115200 bps)
- 1 x Ethernet/IP port (RJ45 connector, 10/100 Mbps adaptive, full/half-duplex mode)
- Data Transfer Capacity:
- Maximum data exchange rate: 100 Mbps (via Ethernet/IP port)
- Profibus-DP: Up to 244 bytes of input data and 244 bytes of output data per communication cycle
- Modbus RTU: Supports up to 1000 registers (32-bit or 16-bit) for read/write operations
ABB AC389AE01 HIEE300888R0001
Technical Specifications
- Input Signal Types: Supports multiple standard analog input signals, including 4-20 mA DC (current), 0-10 V DC (voltage), and ±10 V DC (bipolar voltage)
- Number of Input Channels: 8 independent analog input channels (isolated between channels to prevent signal interference)
- Input Resolution: 16-bit ADC (Analog-to-Digital Converter) for high-precision signal conversion
- Accuracy:
- For 4-20 mA DC: ±0.1% of full scale (FS) at 25°C (ambient temperature)
- For 0-10 V DC/±10 V DC: ±0.1% of full scale (FS) at 25°C (ambient temperature)
- Isolation:
- Channel-to-channel isolation: 500 V AC (rms) for 1 minute
- Module-to-backplane isolation: 1500 V AC (rms) for 1 minute
- Operating Temperature Range: -25°C to +60°C (storage temperature: -40°C to +85°C)
ABB GDB021BE01 HIEE300766R0001
Technical Specifications
- Input Signal Type: Discrete digital signals (dry contact or voltage-driven on/off signals)
- Number of Input Channels: 16 independent digital input channels (isolated per channel or per channel group)
- Input Voltage Range:
- Supported nominal voltages: 24 V DC (standard industrial level)
- Operating voltage tolerance: 19.2 V DC to 30 V DC (to accommodate field power fluctuations)
- Input Current:
- "On" state (active): Maximum 7 mA per channel (at 24 V DC)
- "Off" state (inactive): Maximum 0.1 mA per channel (to minimize power consumption)
- Input Thresholds:
- "On" threshold (voltage to detect active state): ≥16 V DC
- "Off" threshold (voltage to detect inactive state): ≤5 V DC
- Response Time:
- Maximum 1 ms per channel (for fast detection of state changes, critical for time-sensitive control logic)
- Adjustable filter time (0.1 ms to 100 ms) via software to suppress electrical noise