MOXA ICF-1280I-M-ST-T

Manufacturer:​ Moxa Inc. (Taiwan)
Product Brief:​ Converts a standard PROFIBUS DP RS-485 electrical segment to a fiber-optic link, providing galvanic isolation, noise immunity, and extended distance. Intended for connecting PROFIBUS masters/slaves across electrically noisy or geographically separated areas in industrial plants.
Category:
Description
Key Technical Specifications:
  • Model:​ ICF-1280I-M-ST-T (Multi-mode fiber, 2 × ST connectors, -40 to 75 °C operating range)
  • PROFIBUS Interface:
    • 1 × DB9 female (RS-485, PROFIBUS DP pinout per IEC 61158)
    • Baud Rate: 9.6 kbps to 12 Mbps (auto-detect)
    • Bias & Termination: Selectable via DIP switch (120 Ω termination resistor)
  • Fiber Interface:
    • 2 × ST connectors (Multi-mode)
    • Wavelength: 820 nm
    • Typical Link Budget: 14 dB
    • Max Distance: ~ 4 km (multi-mode 62.5/125 µm)
  • Isolation:​ 2 kV built-in on serial side
  • Power Input:​ 12 – 48 V DC (dual redundant inputs), typical consumption < 5 W
  • Power Connector:​ Removable terminal block
  • Housing:​ Metal, IP30
  • Mounting:​ DIN rail (35 mm)
  • Dimensions:​ 39 × 115 × 70 mm (W × H × D)
  • Weight:​ ~ 225 g
  • Operating Temp.:​ -40 °C to +75 °C (Wide Temp. model — suffix T)
  • Standards:
    • EMC: EN 55032 Class A, IEC 61000-4-2/3/4/5/6/8
    • Safety: UL 60950-1, EN 60950-1
    • Hazardous Area: Class I Div 2, ATEX / IECEx (where indicated on label)
  • MTBF:​ > 1,800,000 hrs (Telcordia SR-332)
Functional Features:
  • Transparent PROFIBUS protocol conversion — no addressing or configuration required
  • Link/test LEDs for fiber TX/RX and PROFIBUS activity
  • Redundant DC power inputs with reverse polarity protection
  • Supports point-to-point or redundant ring (if used in pairs) topologies
Application Scenarios:​ Extending PROFIBUS DP to remote skids, linking PLC and VFD/drive clusters across high-EMI areas (near VFD cabinets, welding zones), connecting plant floor to isolated analyzer houses.
Installation & Notes:
  • Set PROFIBUS termination DIP switch ON only at the physical ends of the RS-485 segment.
  • Use proper ST-type multimode patch cords; clean fiber ends before mating.
  • Ensure both ends of the fiber link use matching wavelength and fiber type.
  • Verify LED “Link” is solid green after connection; flashing indicates no partner detected.
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “MOXA ICF-1280I-M-ST-T”

Your email address will not be published. Required fields are marked *

Shipping and Delivery

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.