Emerson DeltaV KJ3223X1-BA1

Product Name:​ Emerson DeltaV KJ3223X1-BA1 Series 2 2-Wire Analog Input Module, 16-Channel, 4–20 mA with HART
Product Introduction:
The KJ3223X1-BA1 is a high-density, 16-channel, 2-wire 4–20 mA analog input (AI) module for the DeltaV system. It receives current-loop signals from field transmitters and optionally communicates with HART-enabled devices for digital parameter access and diagnostics.
Category:
Description
Technical Specifications:
  • Manufacturer:​ Emerson Automation Solutions
  • Model / Part No.:​ KJ3223X1-BA1 (also referenced 12P2871X012)
  • Series:​ DeltaV Series 2
  • Input Channels:​ 16 (2-wire, loop-powered from field device)
  • Input Signal Range:​ 4–20 mA (also supports 0–20 mA / 1–5 mA if configured in software)
  • Resolution:​ 16-bit A/D conversion
  • Accuracy:​ ±0.1 % FS (typical); ±0.2 % over temp
  • Sampling Rate:​ 100 ms per channel (typical scan)
  • HART:​ HART 5/6/7 digital communication supported (via HART modem in terminal block or multiplexer)
  • LocalBus Power:​ 12 V DC, 150 mA typical
  • Field Power (Bussed):​ 24 V DC externally supplied (through terminal block), 600 mA max per carrier
  • Field Circuit Rating:​ 24 V DC, 30 mA per channel typical
  • Open Sensor Detection:​ Yes (< 3.6 mA indicates wire break if enabled)
  • Overrange Capability:​ Up to 21.5 mA readable
  • Hot-Swap:​ Yes
  • Operating Temp:​ -40 °C to +70 °C
  • Certification:​ Class I Div 2, ATEX Zone 2, CE, FM, CSA
  • Weight:​ ~0.18 kg
Functional Features:
  • Automatic channel calibration stored in EEPROM
  • HART variable (PV, SV, TV, CV) readable via DeltaV AMS Device Manager
  • Configurable engineering units, alarm limits, damping
  • Channel-level diagnostics reported to DeltaV alarm summary
Material & Construction:
  • Molded flame-retardant plastic housing (UL94-V0)
  • Gold-plated backplane edge connector
  • Designed for horizontal mounting in DeltaV I/O carrier
Installation & Notes:
  • Requires matching 2-wire AI terminal block (e.g. VE4003 or similar — confirm in DeltaV hardware setup)
  • Ensure field power supply is stable 24 V DC with proper noise filtering
  • Do not mix sourcing and sinking transmitters on same module group unless specified
  • Ground shield at field device or at barrier — not both ends
Applications:​ Pressure, differential pressure, temperature (via transmitter), flow, level — any 4–20 mA loop-connected process measurement in oil & gas, chemical, power, pulp & paper.
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “Emerson DeltaV KJ3223X1-BA1”

Your email address will not be published. Required fields are marked *

Shipping and Delivery

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.