The Simplex 4100-3102 is a dedicated field-mounted auxiliary I/O accessory module engineered exclusively to match the Simplex 4100 series intelligent addressable fire alarm control system. It serves as the intermediate signal conversion and relay switching unit between the main fire alarm controller, field fire detection devices, auxiliary building facility equipment and peripheral notification appliances. The module realizes digital bus signal parsing from the main control unit and converts parsed commands into dry contact switching signals or passive input acquisition signals for external equipment linkage control and status feedback collection.
Category:
Description

Technical Specifications

  • Rated Operating Input Bus Voltage: 24 VDC Nominal Operating Voltage; 18VDC ~ 30VDC allowable working voltage range
  • Bus Communication Protocol: Simplex proprietary IDNet addressable fire bus communication protocol
  • Module Address Allocation: Single unique software programmable bus address per unit, address range fixed 1~240 within single 4100 system bus loop
  • Contact Output Rating: Form C SPDT dry contact relay; Rated resistive load: 5A @30VDC, 3A @120VAC
  • Supervised Input Circuit Rating: Dry contact passive input loop, monitoring current fixed 1.2mA DC supervision current
  • Operating Ambient Temperature Range: 0°C to +50°C operational temperature; -30°C ~ +70°C storage temperature
  • Relative Humidity Working Condition: 5%~95% non-condensing ambient relative humidity
  • Overall Power Consumption Quiescent Standby: 18mA DC quiescent current; 65mA DC maximum in full relay actuation status
  • Enclosure Ingress Protection Grade: IP30 indoor protection rating
  • Module Overall Dimension: 118mm (Height) × 86mm (Width) × 32mm (Depth)

4. Functional Features

  1. Single channel supervised passive input terminal for collecting on/off status feedback signals from fire dampers, exhaust fans, fire shutters and other mechanical fire protection equipment.
  2. Independent single channel Form C relay output for executing linkage startup/shutdown control commands for auxiliary building equipment triggered by fire alarm, pre-alarm or fault signals from main fire panel.
  3. Built-in hardware short-circuit and open-circuit fault automatic identification for the connected input wiring loop, fault signal automatically uploaded to Simplex 4100 main controller via IDNet bus for real-time screen display and historical log recording.
  4. Address parameter configurable directly via Simplex 4100 main panel local keypad programming without dedicated field programming handheld tool.
  5. Integrated dual-color status indicator LED: Red LED for relay output active state; Green LED for normal module powered online status.
  6. Internal hardware surge suppression circuit to block transient voltage spike damage induced by external equipment inductive load switching.
  7. All input/output wiring terminals adopt reverse connection prevention structural design to avoid wiring polarity error induced module burnout.
  8. Supports programmable delay output function via main panel setting, delay time adjustable from 0 second to 300 seconds in 1-second incremental steps.

5. Performance Parameters

  • Input loop fault detection response speed: ≤200ms from wiring open/short fault occurrence to fault report upload to main controller
  • Relay mechanical service life: ≥100,000 full switch cycles under rated load condition
  • Bus communication signal transmission distance: Maximum 3000 meters when using standard 1.5mm² fire-resistant twisted pair bus cable
  • LED indicator service lifespan: ≥50,000 continuous working hours under rated operating voltage
  • Anti-electromagnetic interference compliance: Conforms to EN55022 Class B EMC standard and UL864 fire safety electrical interference specification
  • Data retention: All set module address and linkage configuration parameters permanently stored in internal non-volatile EEPROM chip, no parameter loss after complete module power cut-off

6. Material Composition

  1. Outer housing shell: Flame retardant ABS engineering plastic with UL94-V0 fire resistance grade, anti-aging and anti-corrosion formulation.
  2. Internal printed circuit board (PCB): FR-4 high temperature resistant glass fiber substrate PCB with full tin immersion anti-oxidation coating.
  3. Internal core relay component: Silver alloy contact electromagnetic relay with anti-arc coating on contact surface.
  4. Wiring terminal components: Nickel-plated brass conductive terminals with PA66 flame retardant insulating base.
  5. Internal electronic components: Industrial grade semiconductor chip, solid-state surge suppression diode, metal film fixed precision resistors and multilayer ceramic capacitors.

7. Structural Characteristics

  1. Split type integrated structure including outer plastic enclosure and internal fixed PCB core assembly, modular snap-fit shell design for rapid on-site opening and wiring operation.
  2. Pre-reserved standardized DIN rail clamping buckle on rear shell for direct DIN35 standard mounting rail installation.
  3. Front panel centralized layout of status LED indicators and terminal marking printed label, input terminal area and output terminal area physically partitioned via plastic isolation rib.
  4. Internal PCB fixed via four integrated plastic positioning pillars inside enclosure to avoid circuit board vibration displacement during building equipment operation vibration.
  5. Pre-punched cable inlet reserved at bottom of plastic casing for external wiring penetration, with built-in rubber wire clamping grommet for wire fixation and dustproof sealing.

8. Working Principle

  1. Bus Signal Receiving Phase: The IDNet fire bus from Simplex 4100 main control panel transmits digital coded commands and system power supply to 4100-3102 module; internal bus transceiver circuit isolates and decodes bus digital signals to extract address matching instructions for the module.
  2. Input Signal Collection Phase: External field equipment dry contact feedback wiring connects to supervised input terminals; internal constant current supervision circuit continuously detects input loop resistance value, resistance abnormal fluctuation caused by open or short wiring triggers fault identification circuit and generates fault coded data to feed back to main panel via communication bus.
  3. Output Control Execution Phase: After receiving valid startup/shutdown command matching its pre-set address from main controller, internal MCU drives built-in Form C relay coil to complete contact pull-in or release action, realizing external load equipment circuit switching via relay dry contact terminals.
  4. Status Feedback Loop Phase: Real-time working status of relay output is synchronously sampled by internal detection circuit, all normal, fault and actuation status data is periodically uploaded to Simplex 4100 host for real-time system status monitoring and event log storage.

9. Advantage Highlights

  1. Full original factory matching certification with Simplex 4100 fire alarm host system, zero compatibility error during system integration, no firmware upgrade conflict with original system equipment.
  2. Built-in full wiring fault automatic monitoring for input channel, eliminating hidden safety risk caused by hidden wiring damage of traditional non-supervised relay modules.
  3. Compact small-size body design saves fire control cabinet and field mounting box internal installation space compared with split external relay accessories.
  4. Wide allowable input voltage fluctuation range adapts to unstable site 24VDC standby battery power supply voltage drop under emergency power failure scenarios.
  5. Standardized DIN rail universal mounting structure compatible with global mainstream fire control cabinet internal mounting specifications.
  6. Strict UL864 listed fire safety certification and relevant international fire protection product certification, meeting global fire engineering acceptance inspection standards.
  7. Low quiescent power consumption reduces overall fire alarm system standby battery power load, extending emergency backup power continuous working duration of entire fire system.

10. Applicable Industries

  • Commercial high-rise building industry: Office buildings, shopping malls, hotel complexes and comprehensive commercial plazas fire protection linkage system construction
  • Industrial manufacturing industry: Electronics manufacturing plants, chemical non-explosive production workshops, warehouse storage facilities fire interlock control system
  • Public building industry: Hospitals, schools, stadiums, subway station auxiliary fire equipment linkage matching
  • Residential construction industry: High-rise residential building fire smoke exhaust fan and fire rolling shutter linkage control
  • Transportation industry: Airport terminal buildings, railway station passenger building fire auxiliary equipment control system
  • Institutional construction: Government office buildings, museum and library fire protection automation control engineering

11. Model Series Affiliation

Parent Product Series: Simplex 4100 Intelligent Addressable Fire Alarm Control System Accessory Series
  • Corresponding matching main control panel model range: Simplex 4100-9102, 4100-9202, 4100-9302 main fire alarm controllers
  • Related sibling module models within same accessory series: 4100-3101 (Single non-supervised relay output module), 4100-3103 (Dual-channel I/O combination module), 4100-3201 multi-input monitor module

12. Installation Requirements

  1. Install location requirement: Indoor dry, ventilated non-explosive ambient environment; prohibited for installation inside high-temperature boiler room, high-humidity underground pool room and corrosive gas concentrated equipment room.
  2. Mounting fixation mode options: DIN35 standard top-hat rail clamping installation inside fire control junction box or direct screw fixed mounting on flat insulating mounting plate.
  3. Wiring specification requirement: System IDNet communication bus must adopt twisted pair fire-resistant copper cable with cross-sectional area ranging 1.0mm²~2.5mm²; external input/output control wiring shall use 0.75mm²~2.5mm² insulated fire-proof control cable.
  4. Installation spacing requirement: Minimum 15mm clearance space reserved around module housing for natural heat dissipation, multiple adjacent modules installed with ≥10mm gap between each casing.
  5. Enclosure installation environment: When installed inside field wall-mounted junction box, junction box internal usable volume must exceed 3 times the module overall volume to avoid heat accumulation.
  6. Grounding specification: Module internal functional grounding terminal must connect to fire system dedicated protective earth ground bus with independent grounding wire, prohibited shared grounding wire with power distribution cabinet strong current circuit.

13. Operation & Usage Precautions

  1. Strictly prohibit connecting external AC high voltage load exceeding relay rated contact parameter to module output terminals; over-rated load connection causes permanent relay contact burnout and module failure.
  2. All wiring construction must complete under full power-off status of Simplex 4100 main panel and module bus power supply; live wiring leads to internal circuit board component breakdown.
  3. Avoid direct liquid splashing, dust accumulation and chemical solvent corrosion on module outer casing during long-term site operation; regular quarterly dust cleaning via dry lint-free cloth only, no liquid detergent cleaning allowed.
  4. Any module address modification operation must be finished via authorized Simplex 4100 system qualified operator with system programming access permission, random address tampering results in entire system linkage logic disorder.
  5. If inductive loads such as AC contactor coils are connected to output terminals, auxiliary freewheeling surge absorption diode must be installed in parallel at load terminal as external surge protection per factory specification.
  6. Storage of spare unused modules requires sealed packaging storage under 10°C~35°C dry environment, prohibited long-term open-air placement under high temperature and damp outdoor environment.
  7. In case of module permanent fault damage during usage, only original Simplex factory replacement part is allowed; third-party refurbished or substitute modules cannot access into certified 4100 fire alarm system for formal engineering operation.
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “Simplex 4100-3102”

Your email address will not be published. Required fields are marked *

Shipping and Delivery

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.