Technical Specifications
- Input Electrical Parameters: Dual selectable AC input 115 V AC / 230 V AC, 50/60 Hz
- Rated Input Current: 4.5 A (115 V AC mode), 2.5 A (230 V AC mode)
- DC Output Standard: Fixed 28 V DC regulated output
- Rated Output Load Current: 9 A continuous full-load output
- Output Voltage Adjustable Range: 21 V DC ~ 29 V DC via front panel trim potentiometer
- Maximum Output Power: 252 W nominal full-load power
- Ripple Noise Voltage: < 15 mV RMS under 100% rated load
- Efficiency Rating: 89% typical conversion efficiency at 230 V AC full load
- Form Factor: Vertical wall-mounted enclosed metal cabinet power supply
- Physical Dimensions: 220 mm (H) × 130 mm (W) × 75 mm (D)
- Net Weight: 1.75 kg
Functional Features
- Dual AC input voltage selector switch compatible with global industrial power grid standards
- Multi-stage overvoltage, overcurrent, short-circuit and over-temperature hardware protection circuit
- Front panel output voltage fine-tuning potentiometer for on-site DC output calibration
- Dedicated ALARM relay dry contact signal output for remote power supply fault monitoring
- Terminal block wiring interface for AC input, DC output and fault alarm signal connection
- Internal active power factor correction (PFC) circuit reducing grid harmonic pollution
- Wide operating temperature range supporting non-air-conditioned factory cabinet deployment
- Built-in input surge suppression filter to resist industrial grid voltage spike interference
Performance Parameters
- Line regulation error: ≤ 0.15% across full AC input voltage range
- Load regulation error: ≤ 0.5% from 0% to 100% rated output load
- Temperature coefficient: ≤ 0.02% per °C output voltage drift
- Overcurrent protection trigger threshold: 11 A DC output current
- Short-circuit protection mode: Automatic hiccup intermittent restart after fault clearance
- Hold-up time under full load: > 20 ms during AC input power interruption
- Dielectric withstand voltage: 2000 V AC between input and output isolation circuit
- Operating temperature range: -10 °C ~ +60 °C
Material Composition
- Outer enclosure: Thick cold-rolled steel sheet fully enclosed structure, matte black anti-corrosion paint coating
- Internal heat sink: Aluminum extrusion heat dissipation fin assembly for power switching MOSFET components
- Wiring terminals: Green PA66 flame-retardant plastic terminal blocks with copper alloy conductive contacts
- Internal PCB substrate: High-temperature FR-4 industrial circuit board
- Cooling fan: Ball bearing axial cooling fan with dust filter screen on enclosure ventilation holes
- Isolation components: High-voltage isolation transformers and ceramic safety capacitors
Structural Characteristics
- Vertical wall-mounted fixed structure with four rear mounting screw holes for cabinet interior installation
- Front panel centralized layout of AC voltage selector switch, voltage trim potentiometer, power running and fault alarm LED indicators
- Separate isolated wiring compartments for AC input terminals and DC output/alarm terminals to avoid high-voltage leakage risk
- Uniform array of ventilation perforations on left and right enclosure side panels for forced fan airflow circulation
- Internal metal partition separating high-voltage AC input circuit and low-voltage DC output circuit
Working Principle
Industrial alternating current grid voltage enters internal EMI filter circuit to eliminate power line surge and high-frequency interference, then transmits to active PFC correction circuit to stabilize input power factor and suppress harmonic distortion. The corrected AC voltage is converted to high-frequency square wave via power switching MOSFET tubes, stepped down to 28 V DC nominal voltage through high-isolation transformer, then filtered by secondary LC filter circuit to output stable low-ripple DC power to control system loads. Real-time voltage, current and internal temperature monitoring chips continuously detect operating state; protection circuits cut power conversion channel immediately when parameter exceeds safe threshold and trigger ALARM relay fault signal output to upper monitoring system.
Advantage Highlights
- Optimized 28 V DC output voltage matching all Metso Valmet process control I/O modules without secondary voltage conversion
- Integrated remote fault alarm dry contact relay realizes centralized cabinet power health monitoring
- Comprehensive multi-layer electrical protection avoids control system equipment damage from grid abnormal voltage and short-circuit faults
- Metal fully enclosed casing with dustproof ventilation design adapts high-dust mining and pulp paper production workshops
- Wide dual AC input range compatible with European, Asian and American industrial power supply standards
- High 89% conversion efficiency reduces internal heat generation and long-term cabinet energy consumption
Applicable Industries
Mining mineral processing control systems, pulp & paper mill automation cabinets, ferrous/non-ferrous metallurgy smelting control stations, cement production process control equipment, water treatment industrial DCS cabinets
Product Series
Metso CPS Industrial Control Power Supply Series (ADC5483-D200136L 28V/9A model, ADC5483-D200418 alternative revision variant)
Installation Requirements
- Mount vertically on cabinet interior metal mounting plate with four rear M4 fixing screws
- Maintain minimum 30 mm clearance left and right of enclosure to ensure cooling fan airflow circulation
- AC input wiring must use 1.5 mm² cross-section copper wire with cabinet protective ground connection
- Adjust front panel voltage trim potentiometer to calibrate DC output to standard 28 V DC before connecting load equipment
- Wire ALARM dry contact terminals to upper cabinet PLC fault monitoring input channel for real-time power failure alert
Use & Maintenance Precautions
- Strictly prohibit DC output load current exceeding rated 9 A continuous full-load capacity
- Clean side panel fan dust filter screen every 3 months to prevent heat accumulation activating over-temperature protection shutdown
- Confirm AC input voltage selector switch matches local grid voltage before power-on operation; mis-setting burns internal power components
- Cut off AC input power supply before disassembling enclosure cover for internal inspection; internal circuits carry dangerous high AC voltage
- Do not install the power supply unit adjacent to heat-generating equipment such as servo drives and contactors
- Short-circuit test of DC output terminal blocks is prohibited; repeated short-circuit triggers permanent damage to secondary circuit chips
Reviews