ICS Triplex T9801 16‑Channel Simplex Non‑Isolated Digital Input Termination Assembly

Technical Specifications

  1. Mechanical Specifications
    • Form Factor: AADvance standard termination assembly (compatible with T9300 backplanes)
    • Dimensions: 112 mm (width) × 70 mm (depth) × 123 mm (height) (4.41 in × 2.76 in × 4.84 in)
    • Weight: 1.0 kg (2.2 lb)
    • Mounting: Plug‑in to T9300 backplanes; tool‑free installation
    • Protection Rating: IP20 (dust and finger contact protection)
    • Housing Material: Powder‑coated metal alloy with flame‑retardant polymer insulators
    • Color: Black (matches AADvance controller chassis for uniform appearance)
    • Connector Type: Locking terminal blocks (screw‑type, 2.5 mm² wire capacity)
Category:
Description
  1. Electrical Specifications
    • Nominal Input Voltage: 24 VDC
    • Voltage Range: 18–32 VDC (backplane‑powered commoned supply)
    • Channel Configuration: 16 non‑isolated channels with commoned power
    • Channel Fusing: 50 mA replaceable fuses (part number: T9901, pack of 20)
    • Max Input Current per Channel: 6.5 mA
    • Common Bus Current Capacity: 2.0 A (max)
    • Backplane Current Draw: 80 mA (max)
    • Power Consumption: 1.9 W (max)
    • Heat Dissipation: 6.5 BTU/hour
  2. Environmental Specifications
    • Operating Temperature: -20°C to +70°C (-4°F to 158°F)
    • Storage Temperature: -40°C to +85°C (-40°F to 185°F)
    • Relative Humidity: 10%–95% (non‑condensing)
    • Vibration Resistance: Compliant with IEC 60068‑2‑6 (2 g, 10–150 Hz)
    • Shock Resistance: Compliant with IEC 60068‑2‑27 (15 g, 11 ms duration)
    • EMI/RFI Immunity: Compliant with EN 61000‑6‑2 (industrial immunity) and EN 61000‑6‑4 (industrial emissions)
    • Altitude: Up to 2000 m (6562 ft) without derating
  3. Compliance & Compatibility
    • Compliance: CE marked; UL listed for industrial control equipment; IEC 61508 SIL 3 certified (single‑channel)
    • System Compatibility: AADvance controller systems; T9100 processor base units; T9300 3‑slot backplanes; T9401/T9402 digital input modules
    • Configuration Support: AADvance Engineering Tool (v4.0+) for diagnostic monitoring
    • Redundancy Support: Simplex (non‑redundant) configuration only
    • Regulatory Approvals: RoHS compliant; compliant with ANSI/ISA 84.00.01 safety standards
  4. Performance Specifications
    • Channel Response Time: <1 ms (field input to module signal transfer)
    • Fault Detection: Fuse blow detection; open/short circuit monitoring (via connected T9401/T9402 module)
    • Isolation: Non‑isolated (commoned power bus); channel‑to‑chassis isolation: 500 VDC
    • Fuse Type: 50 mA fast‑acting for overcurrent protection

Functional Features

  1. 16 Non‑Isolated Commoned Channels: Centralizes field wiring for 16 digital input devices with a shared power bus for simplex applications.
  2. SIL 3 Compliance Support: Enables single‑channel IEC 61508 SIL 3 certification when paired with T9401/T9402 modules.
  3. 50 mA Channel Fusing: Protects modules and field devices from overcurrent damage with replaceable T9901 fuses.
  4. Commoned Power Distribution: Delivers 24 VDC (18–32 VDC range) to all channels for simplified wiring and power management.
  5. Plug‑and‑Play Installation: Mounts quickly to T9300 backplanes without specialized tools for fast deployment.
  6. Field Wiring Consolidation: Reduces wiring complexity by terminating multiple field devices in a single assembly.
  7. Diagnostic Integration: Works with T9401/T9402 modules to report open/short circuits and fuse failures via AADvance Engineering Tool.
  8. IP20 Protection: Maintains dust and finger contact protection during operation and maintenance.
  9. EMI/RFI Immunity: Shields signals from electromagnetic interference for reliable data transmission.
  10. RoHS Compliance: Meets environmental standards for hazardous substance restrictions.
  11. Screw‑Type Terminal Blocks: Accommodates 2.5 mm² wires for secure, vibration‑resistant connections.
  12. AADvance System Compatibility: Integrates seamlessly with T9300 backplanes and T9100 processors for end‑to‑end system functionality.

Application Scenarios

  1. Oil & Gas ESD Sensor Monitoring: Terminates ESD sensor wiring (pressure switches, flame detectors) in offshore platforms, using 50 mA fuses to protect T9402 modules and support SIL 3 safety loops.
  2. Chemical Plant Valve Position Feedback: Interfaces limit switch wiring for isolation valve position monitoring, centralizing 16 feedback signals to simplify loop testing and maintenance.
  3. Power Generation Turbine Alarm Contacts: Connects alarm contacts (overspeed, vibration, temperature) to T9401 modules, ensuring fast signal transfer (<1 ms) for rapid turbine shutdown.
  4. Pharmaceutical Batch Process Monitoring: Terminates proximity switch wiring for equipment position sensing in FDA‑compliant facilities, using commoned power to reduce wiring costs and complexity.
  5. Marine Offshore Fire & Gas Detection: Consolidates fire detector and gas sensor wiring in harsh marine environments, with a rugged housing that withstands saltwater mist and vibration.
  6. Mining Conveyor Safety Interlocks: Interfaces emergency stop and guard door interlock wiring, protecting modules from overcurrent via channel fuses and ensuring reliable safety monitoring.

Additional Information

  • Origin: United States
  • Warranty: 12‑month warranty for new original units; extended support via Rockwell Automation service contracts
  • Compatibility: AADvance controller systems, T9300 backplanes, T9100 processors, T9401/T9402 digital input modules, AADvance Engineering Tool (v4.0+)
  • Installation: Plug into T9300 backplane; wire field devices to terminal blocks; configure fuses and diagnostics via AADvance Engineering Tool
  • Maintenance: Replace blown T9901 fuses as needed; inspect terminals quarterly for tightness; clean housing to maintain IP20 protection
  • Accessories: T9901 50 mA replacement fuses (pack of 20); terminal block labels for channel identification
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “ICS Triplex T9801 16‑Channel Simplex Non‑Isolated Digital Input Termination Assembly”

Your email address will not be published. Required fields are marked *

Shipping and Delivery

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.