ProSoft AN-X2-AB-DHRIO

Product Overview

AN-X2-AB-DHRIO is a DIN rail-mounted industrial communication gateway that executes bidirectional protocol translation between legacy Allen-Bradley DH+ (Data Highway Plus) / Remote I/O industrial networks and modern EtherNet/IP Ethernet control networks. It enables seamless integration of legacy PLC-5, SLC 500, and Remote I/O racks into contemporary EtherNet/IP PAC, HMI, and SCADA systems without full legacy hardware replacement.

ProSoft AN-X2-AB-DHRIO EtherNet

  • Technical Specifications
    • Power Supply Parameters
      • The typical power consumption is 200mA at 12V DC or 100mA at 24V DC, with a maximum power consumption of 2.4W. It adapts to the common low - voltage DC power supply environment in industrial sites and has low overall energy consumption.
    • Communication Parameters
      • It is equipped with one RJ45 10/100 Mbps Ethernet port and one DH+/Remote I/O port. It supports DH+, Remote I/O and EtherNet/IP protocols and now supports DH+ migrations on SLC networks.
      • It supports all DH+ and Remote I/O baud rates, which are 57.6k baud, 115.2k baud and 230.4k baud, and Remote I/O addressing ranges from 0 to 76 octal.
    • Environmental and Physical Parameters
      • The operating temperature ranges from 0°C to 50°C, and the storage temperature ranges from -40°C to 85°C. It can withstand extreme temperature changes in both indoor and outdoor industrial environments.
      • The relative humidity tolerance is 5% to 95% non - condensing. Its dimensions are 107mm x 126mm x 34mm excluding connectors, and it weighs approximately 310 grams. It supports DIN rail mounting for convenient integration into industrial control cabinets.

ProSoft ILX56-MM

Product Name: Multi-Master Communication Module Product Description: The ILX56-MM is an in-chassis multi-master communications module designed for Rockwell Automation ControlLogix and CompactLogix PLC platforms. It enables multiple Modbus TCP/IP masters to communicate with slave devices concurrently, simplifying integration of Modbus field equipment into Allen‑Bradley control systems.

ProSoft MVI56-MCM

Product Name:​ MVI56 Series Modbus® Master/Slave Communication Module for Allen-Bradley ControlLogix®
  • Brief Introduction:​ A single-slot, backplane-compatible communication module for Rockwell Automation ControlLogix 1756 racks. It enables the ControlLogix processor to act as a Modbus RTU/ASCII Master (polling up to 247 slaves) or Slave on two independently configurable serial ports.

ProSoft MVI56-MDA4 MDA Scientific CM4 Gas Analyzer Master Module

Technical Specifications
  • Mechanical and Backplane Specifications
    • It is compatible with the 1756 backplane, adopts a single - slot design, and can be installed in both local and remote racks of ControlLogix chassis. It is recognized as a standard input and output module by the ControlLogix system and can access the processor memory smoothly.
  • Electrical Parameters
    • The input voltage ranges from 110V AC to 240V AC, and the operating frequency is 50Hz or 60Hz. The maximum power consumption does not exceed 5W, which shows low energy consumption and has little impact on the overall power load of the industrial control system.
  • Communication and Measurement Parameters
    • It supports Modbus RTU and Modbus ASCII communication protocols, is equipped with two RS - 232 communication ports for connecting to CM4 gas analyzers, and an RJ45 serial port for configuration operations.
    • The sampling rate can reach up to 10Hz. For common gases, the measurement range includes 0 - 25% volume for oxygen and 0 - 20000 ppm for carbon monoxide, with a measurement accuracy of ±0.5%.

ProSoft MVI56-MNETR Modbus TCP

  • Technical Specifications
    • Mechanical and Power Parameters
      • It adopts a single-slot design compatible with the Controllogix 1756 backplane, enabling easy installation into Controllogix chassis without occupying excessive space.
      • The backplane current load reaches 800 mA under 5 VDC and 3 mA under 24 VDC, matching the power supply requirements of Controllogix systems for stable operation.
    • Communication Parameters
      • It is equipped with a 10/100 Mbps Ethernet interface with auto-crossover detection, using an RJ45 connector suitable for Cat5 cables, and it supports Ethernet/IP pass-through communication.
      • It supports storage and transfer of up to 5000 16-bit registers with the Controllogix processor through block transfer or side-connect interface. Client parameters are configurable, including a minimum response delay ranging from 0 to 65535 milliseconds, and it also supports floating-point data types.
    • Environmental and Display Parameters
      • The operating temperature ranges from 0 °C to 60 °C, and the storage temperature ranges from -40 °C to 85 °C. It can operate normally in 5% to 95% relative humidity environments without condensation.
      • It is equipped with a 4-character scrolling alphanumeric LED display that shows module version, IP address, application port settings and error information, along with LED indicators for module status, application status and error status.

ProSoft MVI56-PDPMV1 PROFIBUS DP-V1 Master Network Interface Module for ControlLogix

  • Technical Specifications
    • Power and Physical Parameters
      • It is compatible with the 1756 backplane and occupies a single slot. The backplane current load is 800 mA at 5.1 VDC and 3 mA at 24 VDC, matching standard ControlLogix chassis power supply configurations.
      • The operating temperature range is 0°C to 60°C, and the storage temperature range is -40°C to 85°C. It can operate normally in an environment with 5% to 95% relative humidity without condensation.
      • It resists 30g operational shock and 50g non-operational shock, and can withstand 5g vibration within the frequency range of 10Hz to 150Hz, adapting to harsh industrial site conditions.
    • Communication Parameters
      • It supports all standardized PROFIBUS baud rates, with the maximum baud rate reaching 12 Mbps, meeting the requirements of high-speed data transmission in industrial scenarios.
      • It can connect up to 125 slave devices and can access PROFIBUS PA slaves through DP/PA couplers or links. It also allows multiple master modules to be installed in a single rack to expand network capacity.
      • It is equipped with an RS-232 configuration port with an RJ45 interface, and comes with an RJ45 to DB-9 male cable for on-site configuration and debugging.
    • Software Compatibility Parameters
      • It works with ProSoft Configuration Builder software, supporting functions such as importing project-specific GSD files and automatic bus parameter calculation.
      • It uses ladder logic for data transfer between the module and the processor, and a sample ladder file with add-on instructions is provided to simplify the configuration process for users.
      • It supports communication with configuration software via Ethernet routing through Rockwell Automation Ethernet interfaces such as 1756-ENBT and 1756-EN2T.

ProSoft MVI56-PDPS PROFIBUS DP Slave Communication Module for ControlLogix

Technical Specifications
  • Mechanical and Power Parameters
    • It adopts a single-slot design compatible with the ControlLogix 1756 backplane, supporting installation in both local and remote ControlLogix racks.
    • The power consumption parameters match ControlLogix chassis requirements: 5 VDC backplane current draw is 800 mA, and 24 VDC current draw is 3 mA, ensuring stable operation without overloading the chassis power supply.
  • PROFIBUS DP Communication Parameters
    • It complies with PROFIBUS DP V0 and V1 standards, supporting baud rates ranging from 9.6 kbps to 12 Mbps for flexible network configuration.
    • The module supports up to 244 bytes of input data and 244 bytes of output data for cyclic communication. For acyclic communication, it supports PROFIBUS DP V1 services, including parameterization, diagnosis and alarm handling.
    • It is equipped with a standard DB9 male PROFIBUS DP connector, compatible with standard PROFIBUS DP cables and connectors, and supports PROFIBUS DP slave addressing from 0 to 125.

ProSoft MVI56E-MNET

Product Name:​ Enhanced Modbus TCP/IP Client/Server Communication Module for ControlLogix.
Product Introduction:​ Single-slot 1756 backplane co-processor that bridges Rockwell ControlLogix PLCs to Modbus TCP/IP Ethernet networks. It runs an embedded RTOS on an ARM Cortex-A8 800 MHz CPU, mapping Modbus registers directly into Logix tag memory through ProSoft AOI instructions without occupying PLC scan time.

ProSoft MVI56E-MNETCR

Product Name:​ ControlLogix Modbus TCP/IP + Serial Multi-Protocol Enhanced Module with Conformal Coating (CR variant).
Product Introduction:​ Variant of MVI56E-MNET adding two fully isolated RS-232/422/485 serial ports alongside one 10/100 RJ45, enabling parallel Modbus RTU/ASCII, DF1 and Modbus TCP conversion in one slot.

ProSoft MVI56E-MNETXT

Product Introduction:​ The MVI56E-MNETXT is a single-slot 1756 backplane co-processor built for Rockwell ControlLogix platforms operating in corrosive, wide-temperature or high-altitude sites. It delivers the same Modbus TCP/IP client/server engine as the standard MVI56E-MNET but adds industrial-grade PCB conformal coating and a -25 °C to +70 °C operating envelope, qualifying it for Logix-XT installations such as desert solar pumping, offshore topside panels, arctic pipeline RTU shelters and steel-mill drive rooms. The module runs an independent embedded processor and never consumes ControlLogix scan time for socket handling.

ProSoft MVI56E-PDPMV1

Product Name:​ PROFIBUS DP-V1 Master Network Interface for ControlLogix.
Product Introduction:​ Single-slot 1756 module acting as a certified PROFIBUS DP-V1 master (IEC 61158) to poll DP-V0/V1 slaves (drives, I/O, encoders) and present cyclic I/O plus acyclic parameter data to the Logix processor asynchronously.